Trafag Sf6 Gas Density Monitor

Zoriver(BeiJing)Technology CO., LTD

Product Description

  • Application
        High voltage technology

     

        Main characteristics

       Gas Density Controller for SF6 and other gases
        Principle:       Reference gas measurement
        Measuring range: 0...1 MPa (0...1000 kPa)
        Output:          floating change-over contact
        Switch point:    adjustment in factory

     

       Main features

        Exact switching following isochore
    ?  Excellent vibration resistance
    ?  No false alarms at low temperatures
    ?  Stainless steel sensor
    ?  Independent, galvanically separated circuits

     

       Ordering information






     

        Specifications

     

        Main characteristics

        Principle:       R eference gas measurement
        Measuring range: 0...1 MPa (0...1000 kPa)
        Output:          floating change-over contact
        Switch point:    adjustment in factory

     

        Accuracy (@ 20°C)
        Switching differential typ.
          Microswitch 20: < 15 kPa
          Microswitch 28/83: < 10 kPa
        Accuracy of the reference Miroswitch from the reference isochore (see page 4)
          -30...+50°C: < 10 kPa(Filling pressure: < 650 kPa)
          -30...+50°C: < 12 kPa(Filling pressure: < 1 MPa)


        Microswitch
        Rating:                   see table
        Resistance of insulation: > 2 MΩ
        Dielectric strength:      2 kV terminal ground
        Life time (mechanical)
          Microswitch 20:         1 Mio. cycles
          Microswitch 28/83:      10 Mio. cycles
        Max. difference from the lowest to the highest
          switching point:        130kPa

     

       Electrical connection
        Male electrical plug:     DIN 43650-A
        Female electrical connector
          Cable-:                6...13 mm
          Terminal screw:         0.5...1.5 mm2

     

       Environmental conditions
        Ambient temperatur:       -40....+80°C
        Media temperature         -40....+80°C
        Protection:
          8711/50/51:             IP54
          8712/21/31/41:          IP00
        Humidity:                 max. 95 % relative
        Vibration
          Min. Difference from switch point: 5 kPa
          20...80 Hz:             4 g
        Shock:                    50g/ 11ms

     

        Security
        Leakage of Reference chamber: < 0.5 kPa/ year
                                      (5·10-10 kPa·I·s-1)
        Service:                      none, switch point checking after 5 years
        Reference chamber leakage tests: With Helium gas in vacuum process
                                      and integral leakage test in overpressure process

     

     

       Mechanical data
        Material
          Sensor:
             Housing:                 1.4435 (AISI316L)
             Filling:                 Gas
          Housing:                    AlMgSi1, anodized
          Male electrical plug:       PA, Polyamid
        Weight:                       ~ 350 g (8711)

     

       Electrical data switch



       Electrical connection





        Dimensions





        Accessories

Company Profile

  • Zoriver(BeiJing)Technology CO., LTD
  • [ China ]
  • This company is registered as a free member and is not verified or authenticated by Tradekey.com
  • China (Beijing) Technology Co., Ltd. is headquartered in Australia Zoriver branches in Beijing, China. Is a collection of various types of pressure, Thermometer development, manufacturing and sales in one of the specialized manufacturing company.  Zoriver in October 2006 to set up offices in Beijing, China; February 2009  China (Beijing) Technology Co., Ltd. was established as Zoriver headquar...

Basic Information

  • Company Products / Services: pressure gauge
  • Year Established: 2000
  • Number of Employees: 100+
  • Website: http://www.zoriver.cn/
Contact Now